When the ambient temperature is below 15C or above 35C the recommended compensation factor is 3mV/C/cell(Floating Charge) or 4mV/C/cell(Cycle) starting from the standard center point of 25C.
Battery temperature in charging should be in the range of -15C to 50C.
Attention
Examine the appearance of the battery before use.
Store the battery in a cool place.
Recharge the battery that has been stored for more than 3 months.
Charge the battery in a well-ventilated environment.
Regularly survey batteries charging voltage to make sure it is in the range of chart 1.
Secure the battery firmly installed in the equipment.
Discharge
Discharge Current / A
Final Discharge Voltage
6V/12V Series
2V Series
0.2c or below
1.75V / cell
1.80V
From 0.2C to 0.5 C
1.70V / cell
1.75V
From 0.5C to 1.0 C
1.55V / cell
1.70V
Above: 1.0 C
1.30V / cell
1.60V
Note:
See the above table, Final Discharge Voltage should vary with the change of discharge current.
Attention: When discharge, the voltage must not be lower than its corresponding final discharge voltage.
Immediate charge after discharge or over-discharge for retaining battery life.
Battery temperature in discharge should be in the range of -15C to 50C.
Prohibitions
Don’t short circuit the battery.
Don’t use the battery in an airtight cabinet.
Don’t disassemble the battery.
Don’t load and unload the battery roughly.
Don’t attempt to use a cracked, deformed, or leaky battery.
Don’t subject the battery to excess vibration or violent joints.